Event Type CID Code Event Source
‘A Key Fire Alarm 1115 500 + Keypad (1 - 6)
Zone Fire Alarm 1110 Zone (1 - 30)
Zone Fire Supervisory 1200 Zone (1 - 28)
Zone Burglar Alarm 1130 Zone (1 - 28)
Zone Burglar Tamper 1137 Zone (1 - 28)
‘B’ Key Holdup Alarm 1120 500 + Keypad (1 - 6)
Zone Holdup Alarm 1120 Zone (1 - 28)
Duress 1121 User (1 - 50)
‘C’ Key Auxiliary Alarm 1100 500 + Keypad (1 - 6)
Zone Auxiliary Alarm 1100 Zone (1 - 28)
Zone CCM Alarm 1150 Zone (1 - 28)
Zone Fire Trouble 1373 Zone (1 - 30)
Zone Fire Test Mode Begin 1604 Zone (1 - 30)
Zone Burglar Trouble 1370 Zone (1 - 28)
Zone Holdup Trouble 1370 Zone (1 - 28)
Zone Auxiliary Trouble 1370 Zone (1 - 28)
Zone Other Trouble 1370 Zone (1 - 28)
Senior Watch Trouble 1641 Zone (1 - 28)
Zone No Response on Bus 1333 Zone (13 - 29)
RF Point Not Reporting 1381 Zone (13 - 28)
Smoke Trouble 1380 Zone (13 - 30)
RF Sensor Tamper 1383 Zone (13 - 28)
RF Point Low Battery 1384 Zone (13 - 28)
Zone Fire Bypass 1571 Zone (1 - 30)
Zone Burglar Bypass 1573 Zone (1 - 28)
Zone Holdup Bypass 1572 Zone (1 - 28)
Zone Auxiliary Bypass 1572 Zone (1 - 28)
Zone Other Bypass 1570 Zone (1 - 28)
Zone Fire Alarm Restore 3110 Zone (1 - 30)
Zone Fire Supervisory Restore 3200 Zone (1 - 28)
Zone Burglar Alarm Restore 3130 Zone (1 - 28)
Zone Burglar Tamper Restore 3137 Zone (1 - 28)
Zone Holdup Alarm Restore 3120 Zone (1 - 28)
Zone Auxiliary Alarm Restore 3100 Zone (1 - 28)
Zone Critical Condition Monitor Alarm Restore 3150 Zone (1 - 28)
Zone Fire Trouble Restore 3373 Zone (1 - 30)
Zone Fire Test Mode End 3604 Zone (1 - 30)
Zone Burglar Trouble Restore 3370 Zone (1 - 28)
Zone Holdup Trouble Restore 3370 Zone (1 - 28)
This section cross-references many of the reporting options and equivalent codes sent by Sentrol-manufactured controls
when transmitting in the Contact ID formats.
Simplified example of data sent in Contact ID format: SSSS 18 Q XYZ AA CCC
Where: SSSS = 4 decimal digit subscriber #
18 = Contact ID que for automation systems
Q = Event qualifier; 1 = new event or opening; 3 = new restore or closing; 6 = previously reported event
XYZ = Event code (3 decimal digits)
AA = Area number (00 for system events)
CCC = Zone, sensor, or user # (3 decimal digits)
Digital Communicator Table For Contact ID Formats